    Autor
    Domínguez Donado, Germán José
    Gómez Silva, José Luis
    Fecha
    2022-12-02
    Resumen
    El sistema de iluminación actual de la biblioteca de la Universidad del Norte es antiguo, ya que está constituido por lámparas y equipos de hace más de 20 años, los cuales no cumplen con las actuales normativas y tienen un impacto ambiental negativo en la huella de carbono. Se proponen 2 soluciones de mejora del sistema de iluminación evaluando los requisitos técnicos del cumplimiento de los niveles mínimos de iluminancia del RETILAP (Reglamento Técnico de Iluminación y Alumbrado Público) y validando la factibilidad energética y económica. La propuesta 1 consiste en el remplazo de los tubos fluorescentes por tubos leds, se logra un ahorro energético del 52,2% con la implementación de esta propuesta y un periodo de retorno de la inversión de 3 años. De la propuesta 2 se realiza el rediseño total, implementando un diseño eficiente energéticamente, con esta propuesta se logra un ahorro de hasta el 57%. Ambas propuestas aplican el uso de control dimerizable mediante la atenuación continua para aprovechar la luz natural que ingresa por las ventanas. Se analizó la reducción de la huella carbono realizando un análisis energético y de las emisiones de C02 que se evitan emitir al reducir el consumo energético.
     
    The current lighting system of the Universidad del Norte library is old, as it is made up of lamps and equipment that are more than 20 years old, which do not comply with current regulations and have a negative environmental impact on the carbon footprint. Two lighting system improvement solutions are proposed, evaluating the technical requirements for compliance with the minimum levels of illuminance of RETILAP (Technical Regulation of Lighting and Public Lighting) and validating the energy and economic feasibility. Proposal 1 consists of replacing fluorescent tubes with LED tubes, an energy saving of 52.2% is achieved with the implementation of this proposal and a payback period of 3 years. From proposal 2, the total redesign is carried out, implementing an energy efficient design, with this proposal a saving of up to 57% is achieved. Both proposals apply the use of dimmable control through continuous dimming to take advantage of the natural light that enters through the windows. The reduction of the carbon footprint was analyzed by performing an energy analysis and the C02 emissions that are avoided by reducing energy consumption.
     
    Colecciones a las que pertenece
    • Proyectos finales Pregrado en Ingeniería Eléctrica [149]
    Imagen Diseño 3D Biblioteca (98.37Kb)