Mostrar el registro sencillo del ítem

MeshX: Computational tool for the evaluation of grounding mesh in the face of fast front currents

dc.contributor.advisorPulgarin Rivera, Juan Diego
dc.contributor.authorIriarte Hernández, D. Alejandro
dc.contributor.authorLópez D’onofrio, Jesús David
dc.date.accessioned2024-06-25T13:34:59Z
dc.date.available2024-06-25T13:34:59Z
dc.date.issued2023-11-30
dc.identifier.urihttp://hdl.handle.net/10584/12144
dc.description.abstractLa seguridad eléctrica en entornos industriales es una preocupación crítica debido a las peligrosas elevaciones del potencial del suelo causadas por corrientes en sistemas de puesta a tierra. Estos riesgos afectan a trabajadores y residentes cercanos a instalaciones eléctricas. MeshX ofrece una solución computacional para evaluar eficientemente el diseño de mallas de puesta a tierra ante impulsos de corriente de frente rápido, un aspecto pasado por alto en el software comercial y las normativas internacionales. Se desarrolló un algoritmo basado en el método electromagnético híbrido (HEM) para calcular las elevaciones de potencial en los nodos del sistema de puesta a tierra. Sin embargo, el proyecto enfrentó limitaciones debido a recursos computacionales y restricciones temporales. MeshX logra calcular las impedancias y elevaciones de potencial, permitiendo la evaluación transitoria de sistemas de puesta a tierra. Facilita la rápida identificación de riesgos potenciales y tiene el plan de ofrecer herramientas para optimizar diseños frente a corrientes de frente rápido, contribuyendo así a mejorar la seguridad eléctrica en entornos industriales.es_ES
dc.description.abstractElectric safety in industrial settings is a critical concern due to hazardous ground potential rises caused by grounding system currents. These risks impact workers and residents near electrical installations. MeshX offers a computational solution to efficiently evaluate grounding mesh designs against fast front current impulses, an overlooked aspect in commercial software and international regulations. An algorithm based on hybrid electromagnetic method (HEM) is developed to compute potential rises at grounding system nodes. This tool aims to aid engineers in assessing potential safety risks and optimizing grounding designs. However, the project faced limitations concerning available computational resources and time constraints, which shaped the scope and depth of the study. MeshX successfully achieves impedance and potential rise calculations, allowing for the transient evaluation of grounding systems. It facilitates quick identification of potential risks and aims to provide a platform for optimizing designs against fast front currents, thereby contributing to enhanced electrical safety in industrial settings.en_US
dc.language.isospaes_ES
dc.publisherBarranquilla, Universidad del Norte, 2023es_ES
dc.rightsUniversidad del Nortees_ES
dc.subjectDescargas atmosféricases_ES
dc.subjectSistema de puesta a tierraes_ES
dc.subjectCorrientes de frente rápidoes_ES
dc.subjectMétodo electromagnético híbridoes_ES
dc.subjectgrounding transientsen_US
dc.subjectlightning surgesen_US
dc.subjectHybrid Electromagnetic Methoden_US
dc.subjectFast Front Currentsen_US
dc.titleMeshX: Herramienta computacional para la evaluación de mallas de puesta a tierra ante corrientes de frente rápidoes_ES
dc.titleMeshX: Computational tool for the evaluation of grounding mesh in the face of fast front currentsen_US
dc.typearticlees_ES
dc.rights.accessRightsopenAccesses_ES


Ficheros en el ítem

No Thumbnail [100%x80]
No Thumbnail [100%x80]

Este ítem aparece en la(s) siguiente(s) colección(ones)

Mostrar el registro sencillo del ítem